This means that locations where the temperature never comes close to 45C are becoming much more attractive than many of the deserts where many datacenters are being built currently. Not having to pay the CAPEX and OPEX for evaporative cooling is a big difference I imagine.
I have developed water cooled car electronics and there we had to work with 80C coolant with peaks to 105C. And MTBF figures had to be low, so this was a big cost driver for the design.
Rule of thumb is that 10 degrees difference makes reactions go, and things fail, twice as fast. This is not exact science, but ballpark is about right.
Evaporative cooling seems to be some American nonsense.
Here in Europe, the only things using evaporative cooling are large power plants and industrial processes needing to shed a lot of heat. Everything else is either using pure air cooling, cooling based on a nearby river, or in extremely modern/research projects, dump their excess heat into district heating systems [1][2].
For me as a German, reading about Americans complain about water usage for datacenters was a real culture shock.
It's not just modern stuff - steel works and other heavy industry used process powered district heating for a very long time. In some cases it created problems when the enterprise went bankrupt or fragmented and suddenly the process that is providing the district heating might no longer be running. :P
This is the dumbest comment line and perpetuates one facet of hate towards datacenter water consumption. Why?
When water evaporates, where does it go?
1. To the void, blinks out of existence to never be seen of again (cool! Violation of conservation of matter/energy)
2. Evaporates into the atmosphere, where it forms as clouds, gaseous water, and condenses to rain
Naturally, the heat is a problem. And running massive fossil fuels is stupid, given we could go all in on solar. But solar also reduces heat effects due to conversion to electricity. Add reflective cooling paint, and we'd be on our way of active cooling electricity generation.
China's doing exactly this. USA? We just open up more closed oil wells, and double down on coal. Smells like, 1800s version of winning with a large dose of cancer.
Frequently, the water that goes into clouds from some place will not return through rain in the same place.
If you evaporate water in a place where it seldom rains, it is likely that you will make that place drier than it already is, so you should avoid this.
Only for datacenters built in rainy places it does not matter whether they evaporate water.
Obviously the water isn't destroyed, but the problem is when you pull water out of some deep aquifer. It make take a Very Long Time before that rain can refill the aquifer. Assuming it falls in the right place and not 1000 miles away.
Globally over very long time horizons datacenter water usage is neutral. But over the shorter time periods that we care about, it moves the water around in problematic ways.
> 2. Evaporates into the atmosphere, where it forms as clouds, gaseous water, and condenses to rain
The problem is, you can do this on say, a large lake. No big deal there, as long as you can manage fouling. Or you can do this on an ocean if you desalinate the water. There, your assumption holds.
But if your water supply is a small river that already has trouble supplying downstream with enough (clean) water? Suddenly the "lost" water is a real issue for the downstream communities depending on it, either because they have to compensate by digging wells into groundwater aquifers that often have replenishment times measured in years if not decades or centuries, or because they have to deal with riverbeds running dry in the worst case, which places them in an even worse bind given they have to discharge the water from sewage treatment plants in a river that can dilute it enough with fresh water.
Friends don't let friends run evaporative cooling if there is literally any other way.
You make a good point. The current USA push for datacenters is more a game of how much they can externalize the costs to everyone else, and internalize all the gains.
Geothermal is great at heat/cooling control. So is electric condensation of atmospheric water. It's a big energy gathering and controlling problem. And more money can reduce or near eliminate the negatives.
The USA companies are not forced to pay appropriately for current great teach for electricity and cooling. They instead force communities to "deal with it".
And no, data centers do not need drinkable water for the compute. We could have had water cleaning, recycling units, etc. Nope, "too expensive".
ASHRAE has a maximum inlet temperature of 45 degrees Celsius. You can order Dell servers configured for this in an air-cooled design. I looked at it for places where proper AC is not readily available or best I could is a fan (mostly industrial facilities with close to no IT).
The Nvidia design is not new, I think here there was a link to a paper a while back discussing the advantages of raising the liquid temperature in liquid-cooled designs.
Now, keep in mind that yes, 45 degrees is quite hot for humans, but if a computer can get to 100 or 150 degrees without cooling, those 45 degrees make the liquid temperature quite cold.
As a parallel, think of the fact that car cooling is done at 90 degrees Celsius. Too hot for humans, but very cool for engines.
Well, it killed the chiller for data centers that have liquid cooled racks. Which is good news, 300-350 watts per ton of cooling is better than 1000 watts per ton of cooling from a chiller.
1 ton of cooling = 12,000 BTU/hr = 3.52 kW thermal cooling
Air handlers in every non data center building will continue using chilled water at 45F to 55F (7C to 13C) to maintain a 55F discharge air temp setpoint during cooling.
No. Similar capex and better opex. Chillers are not very expensive compared to the chips. Data center economics is built around PUE, a ratio of total power / IT power. The optimal data center has PUE=1, a real data center is >1 because some power has to go to facilities and cooling.
I have developed water cooled car electronics and there we had to work with 80C coolant with peaks to 105C. And MTBF figures had to be low, so this was a big cost driver for the design.
I wonder if moving from 30-35 to 45 degrees has an impact on component lifespan
Here in Europe, the only things using evaporative cooling are large power plants and industrial processes needing to shed a lot of heat. Everything else is either using pure air cooling, cooling based on a nearby river, or in extremely modern/research projects, dump their excess heat into district heating systems [1][2].
For me as a German, reading about Americans complain about water usage for datacenters was a real culture shock.
[1] https://www.br.de/nachrichten/bayern/noch-haeufig-ungenutzte...
[2] https://www.bayern-innovativ.de/emagazin/detail/tu-muenchen-...
When water evaporates, where does it go?
1. To the void, blinks out of existence to never be seen of again (cool! Violation of conservation of matter/energy)
2. Evaporates into the atmosphere, where it forms as clouds, gaseous water, and condenses to rain
Naturally, the heat is a problem. And running massive fossil fuels is stupid, given we could go all in on solar. But solar also reduces heat effects due to conversion to electricity. Add reflective cooling paint, and we'd be on our way of active cooling electricity generation.
China's doing exactly this. USA? We just open up more closed oil wells, and double down on coal. Smells like, 1800s version of winning with a large dose of cancer.
If you evaporate water in a place where it seldom rains, it is likely that you will make that place drier than it already is, so you should avoid this.
Only for datacenters built in rainy places it does not matter whether they evaporate water.
Globally over very long time horizons datacenter water usage is neutral. But over the shorter time periods that we care about, it moves the water around in problematic ways.
The problem is, you can do this on say, a large lake. No big deal there, as long as you can manage fouling. Or you can do this on an ocean if you desalinate the water. There, your assumption holds.
But if your water supply is a small river that already has trouble supplying downstream with enough (clean) water? Suddenly the "lost" water is a real issue for the downstream communities depending on it, either because they have to compensate by digging wells into groundwater aquifers that often have replenishment times measured in years if not decades or centuries, or because they have to deal with riverbeds running dry in the worst case, which places them in an even worse bind given they have to discharge the water from sewage treatment plants in a river that can dilute it enough with fresh water.
Friends don't let friends run evaporative cooling if there is literally any other way.
Geothermal is great at heat/cooling control. So is electric condensation of atmospheric water. It's a big energy gathering and controlling problem. And more money can reduce or near eliminate the negatives.
The USA companies are not forced to pay appropriately for current great teach for electricity and cooling. They instead force communities to "deal with it".
And no, data centers do not need drinkable water for the compute. We could have had water cleaning, recycling units, etc. Nope, "too expensive".
The Nvidia design is not new, I think here there was a link to a paper a while back discussing the advantages of raising the liquid temperature in liquid-cooled designs.
Now, keep in mind that yes, 45 degrees is quite hot for humans, but if a computer can get to 100 or 150 degrees without cooling, those 45 degrees make the liquid temperature quite cold.
As a parallel, think of the fact that car cooling is done at 90 degrees Celsius. Too hot for humans, but very cool for engines.
1 ton of cooling = 12,000 BTU/hr = 3.52 kW thermal cooling
Air handlers in every non data center building will continue using chilled water at 45F to 55F (7C to 13C) to maintain a 55F discharge air temp setpoint during cooling.
https://mitchellt.com/2018/10/23/why-is-55-so-important.html
The same set of companies that make chillers are the ones that make dry coolers: Carrier, Daikin, Trane, York (JCI), Liebert (Vertiv)
There's no inherent reason this has to be a hard cut or that a hard cut to a different cooling architecture will be the right way to go.